Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 145

Advertising
background image

Rockwell Automation Publication D2-3518-3 - May 2013

145

Chapter 9

Selects drive action when an analog signal loss is detected on user-configurable
analog input 2:

1.0V = signal loss

1.5V = end of signal loss

2.0 mA = signal loss

3.0 mA = end of signal loss

See

AC Line I/O Board Description (Frame 3 Only) on page 25

through

Combined I/O Board Description (Frame 4 Only) on page 29

for a description

of I/O hardware that is present on this drive and is controlled by the inverter.

One of the selections (1=Fault) stops the drive on signal loss. All other choices
make it possible for the input signal to return to a usable level while the drive is
still running.

327

Analog In 2 Loss

Range:

0 = Disabled
1 = Fault
2 = Hold Input (use last frequency command)
3 = Set Input Lo (use Minimum Speed as frequency command)
4 = Set Input Hi (use Maximum Speed as frequency command)
5 = Goto Preset1 (use Preset1 as frequency command)
6 = Hold OutFreq (maintain last output frequency)

Default:

0 = Disabled

Access:

1

Path: Inputs & Outputs > Analog Inputs

See also:

91, 92, 320, 326, 327

ATTENTION: Setting parameter 327 to a value greater than 1 allows the input
signal to return to a usable level while the drive is running. If a lost analog
signal is restored while the drive is running, the drive ramps to the restored
reference level at the rate specified in Accel Time 1 (140), Accel Time 2 (141),
Decel Time 1 (142), and Decel Time 2 (143). Be aware that an abrupt speed
change may occur depending upon the new reference level and the rate
specified in these parameters. Failure to observe this precaution could result in
bodily injury.

IMPORTANT

Note that there is no signal loss detection while the input is in bipolar voltage
mode.