Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 114

Advertising
background image

114

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 9

Sets the time that the inverter remains in its power loss state before the Power
Loss fault (fault 3) is issued.

If the Power Loss fault is not enabled using the inverter Fault Config 1 parameter
(238), the value of Power Loss Time (185) has no effect on the detection of or
response to a power loss condition.

When set to a non-zero value, selects the change in DC Bus Voltage level at
which the Power Loss occurs.

This value of this parameter is ignored unless one of the digital inputs is
configured to the Pwr Loss Lvl function using the inverter Digital In

x Sel

parameters (361...366).

In Liquiflo 2.0 drives, this parameter should not be changed from its default, and
the digital inputs should not be configured to the Pwr Loss Lvl function.

Selects the source for control of drive direction.

185

Power Loss Time

Range:

0.0...60.0 sec [0.1 sec]

Default:

0.0 sec

Access:

0

Path: Dynamic Control > Power Loss

See also:

184, 238

186

Power Loss Level

Range:

0.0...999.9 [0.1V DC]

Default:

0.0V DC

Access:

1

Path: Dynamic Control > Power Loss

See also:

184, 361...366

190

Direction Mode

Range:

0 = Unipolar
1 = Bipolar
2 = Reverse Dis

Default:

2 = Reverse Dis

Access:

0

Path: Utility > Direction Config

See also:

320...327, 361...366

ATTENTION: Setting parameter 190 to 0 or 1 may cause unwanted motor
direction. Verify driven machinery cannot be damaged by reverse rotation
before changing the setting of this parameter to 0 or 1. Failure to observe this
precaution could result in damage to, or destruction of, equipment.

Advertising