Chapter 9

The imbalance in input phase current is displayed as

x.x%.

The imbalance in amps is calculated as the larger of:

(largest phase current) – (average phase current), or

(average phase current) – (smallest phase current).

The imbalance in percent is calculated as:

(Imbalance in amps) ÷ (average phase current) x 100.

The imbalance in input phase voltage is displayed as

x.x%.

The imbalance in volts is calculated as the larger of:

(largest phase to phase voltage) – (average phase to phase voltage), or

(average phase to phase voltage) – (smallest phase to phase voltage).

The imbalance in percent is calculated as:

(Imbalance in volts) ÷ (average phase to phase voltage) x 100.

The rectifier rated kW is displayed as

x.xx kW.

22

Line I Imbalance

Range:

0.0...100.0% [0.1%]

Default:

Read Only

Access:

0

Path: Monitor > Metering

See also:

2, 3, 4, 62, 63

23

Line V Imbalance

Range:

0.0...100.0% [0.1%]

Default:

Read Only

Access:

0

Path: Monitor > Metering

See also:

7, 8, 9, 60, 61

26

Rated kW

Range:

0.00...3000.0 kW [x.xx kW]

Default:

Read Only

Access:

0

Path: Monitor > Drive Data

See also: