About alarms – Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 198

Advertising
background image

198

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 10

Table 15 - Inverter Status LED Definitions

Table 16 - Rectifier Status LED Definitions

Table 17 - Status LED Definitions for Hardware Failure

About Alarms

Alarms indicate conditions that may affect drive operation or application
performance.

There are two alarm types, as described in

Table 18

.

Color

State

Description

Green

Flashing

Drive ready, but not running and no faults or alarms are present.

Steady

Drive running, no faults or alarms are present.

Yellow
See

About Alarms on

page 198

.

Flashing

The drive is not ready. Check inverter parameter 214 (Start Inhibits).

Steady

An alarm condition exists; drive may be running. Check inverter
parameters 211 (Drive Alarm 1) and 212 (Drive Alarm 2).

Red
See

About Faults on

page 201

.

Flashing

A fault has occurred.

Steady

A non-resettable fault has occurred.

Color

State

Description

Green

Flashing

Rectifier ready, but not running and no faults are present.

Steady

Rectifier running (providing current to inverter).

Yellow

Flashing

Precharge contactor is open and rectifier is not running. This is the
normal state if the inverter is not running.

Steady

A rectifier alarm condition exists; rectifier may be running. Check
rectifier parameter 211 (Alarm Status).

Red

Flashing

A rectifier fault has occurred. This also causes an inverter fault, and
the fault is enunciated on the OIM or other DPI device.

Steady

A non-resettable rectifier fault has occurred.

IMPORTANT

Certain hardware failures produce indications on the status LEDs that are not
covered in the above tables. For Frame 3 drives, the appropriate response to the
appearance of any of these indications is to replace either the Rectifier Control
board or Inverter Control board depending on which LED displays the
indication. For Frame 4 drives, the appropriate response is always to replace
the Control board.

Table 17

lists the indications.

LED Indication

Condition

Red/green alternating

Control board boot firmware is running because control board
application firmware is corrupted.

Yellow/green/red repeating pattern

Control board RAM has failed or control board boot firmware is corrupted.

Advertising