224 fault frequency, 225 fault amps, 226 fault bus volts – Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 126: 227 status 1 @ fault

Advertising
background image

126

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 9

The imbalance in percent is calculated as:

(Imbalance in amps) ÷ (average phase current) x100.

Captures and displays the output frequency of the drive at the time of the last
fault.

Captures and displays RMS motor amps at the time of the last fault.

Captures and displays the DC bus voltage of the drive at the time of the last fault.

Captures and displays Drive Status 1 bit pattern at the time of the last fault.

Figure 53 - Status 1 @ Fault (227)

224

Fault Frequency

Range:

+/-400.0 Hz [0.1 Hz]

Default:

Read Only

Access:

1

Path: Utility > Diagnostics

See also:

225...230

225

Fault Amps

Range:

0.0...3276.7 A [0.1 A]

Default:

Read Only

Access:

1

Path: Utility > Diagnostics

See also:

224...230

226

Fault Bus Volts

Range:

0.0...3276.7V DC [0.1V DC]

Default:

Read Only

Access:

1

Path: Utility > Diagnostics

See also:

224...230

227

Status 1 @ Fault

Range:

See

Figure 53

Default:

Read Only

Access:

1

Path: Utility > Diagnostics

See also:

209, 224...230

0 0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Condition True
0 =Condition False
x =Reserved

Bit #

Ready

Activ

e

Command Dir

Actual Dir

Acceler

ating

Deceler

ating

Alar

m

Faulted

At Speed

Local ID 0

Local ID 1

Local ID 2

Spd Ref ID 0

Spd Ref ID 1

Spd Ref ID 2

Spd Ref ID 3

Nibble 1

Nibble 2

Nibble 3

Nibble 4