Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 112

Advertising
background image

112

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 9

Defines the analog input level that stops the drive. This parameter is not used
with LiquiFlo 2.0 AC drives.

Defines the amount of time at or below Sleep Level before a stop command is
issued. This parameter is not used with LiquiFlo 2.0 AC drives.

Sets the reaction to a loss of input power. If Power Loss Mode is set to:

Coast

or Coast Input

Rectifier can no longer synchronize to the AC line, or

DC bus voltage is

73% of its value at the time of the input power loss.

Decel

, Decel Input, or Decel Fault

Rectifier can no longer synchronize to the AC line, or

DC bus voltage is

82% of its value at the time of the input power loss.

Continue

Rectifier can no longer synchronize to the AC line, or

DC bus voltage is

305V DC.

182

Sleep Level

Range:

4.000 mA, 0.000V / Wake Level [0.001 mA, 0.001V]

Default:

5.000 mA, 5.000V

Access:

1

Path: Dynamic Control > Restart Modes

See also:

183

183

Sleep Time

Range:

0.0...30.0 [0.1 sec]

Default:

1.0

Access:

1

Path: Dynamic Control > Restart Modes

See also:

182

184

Power Loss Mode

Range:

0 = Coast
1 = Decel
2 = Continue
3 = Coast input (same as Coast in Liquiflo 2.0 drives)
4 = Decel input (same as Decel in Liquiflo 2.0 drives)
5 = Decel fault

Default:

0 = Coast

Access:

0

Path: Dynamic Control > Power Loss

See also:

185, 169, 190, 238, rectifier 64, rectifier 65