Rockwell Automation Publication D2-3518-3 - May 2013

203

Chapter 10

Clearing Faults

A fault condition can be cleared by the following:

1.

Press

or any F-Key to acknowledge the fault and remove the fault

pop-up from the OIM screen.

2.

Address the condition that caused the fault. The cause must be corrected
before the fault can be cleared.

3.

After corrective action has been taken, clear the fault using one of the
following:

Setting Fault Clear (240) to Clear Faults (1).

Issuing a Stop-Clear Faults command from the control device (such as
an OIM). This action only succeeds if the clear faults function for that
device is enabled using the Logic Mask (276) and Fault Clr Mask (283).

Resetting faults clears the faulted status indication. If any fault condition still
exists, the fault is latched, and another entry made in the fault queue.

Note that performing a fault reset does not clear the fault queue. Clearing the
fault queue is a separate action. See the Fault Clear (240) parameter description.

Fault Descriptions and Corrective Actions

Frame 3 Fault Descriptions and Corrective Actions

Table

describes drive faults and corrective actions for Frame 3 (firmware version

1.x only). It also indicates if the fault is:

1

Auto-resettable, and can also be reset using normal fault clearing mechanisms

2

Non-resettable

3

User-configurable, and can be reset using normal fault clearing mechanisms

4

Normal fault*

*The fault is resettable using normal fault clearing mechanisms on the drive
(Stop/Reset button, powercycling, etc.) or through VS Utilities.

IMPORTANT

Read all faults from the inverter. Although rectifier faults occur, they are
displayed on the inverter.