Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 158

Advertising
background image

158

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 9

If this input function is open, the integrator for the Process PI loop is allowed to
increase.

28 = PI Reset:

If this input function is closed, the integrator for the Process PI

loop is reset to 0.

If this input function is open, the integrator for the Process PI loop integrates
normally.

29 = Pwr Loss Lvl: Do not

select the Pwr Loss Lvl input function in

Liquiflo 2.0 drives.

30 = Precharg En:

This input function is used to manage disconnection from a

common DC bus. Do not select the Precharg En input function in Liquiflo 2.0
drives.

Type 2 Alarms

Some digital input programming may cause conflicts that result in a Type 2
alarm. For example, Digital In1 Sel set to 5 (Start) in 3-wire control, and Digital
In2 Sel set to 7 (Run) in 2-wire control. See

Chapter 10

for more information

about these alarms.

Dig In Status (116) indicates the current state of the digital inputs.