Configure and Start Up the Kinetix 300 Drive

Chapter 6

Table 64 - Analog Velocity

Table 65 - Analog Current

ID

Parameter Name

Description

Value

266

Drive Mode

Set to Analog Velocity

4

36

VelocityScale

Analog input velocity reference scale:
Velocity = Vinput x VelocityScale

Range: -10000…10000 rpm/V

76

AccelLimit

Accel value for Velocity mode

Range: 0.1…5,000,000 UU/s

77

DecelLimit

Decel value for Velocity mode

Range: 0.1…5,000,000 UU/s

75

EnableVelAccDec

Enable Accel/Decel function for Velocity mode

0 = Disable
1 = Enable

89

AnalogInput1Deadband

Analog input dead-band. Applied when used as a
velocity reference.

Range: 0…100 mV

90

AnalogInput1Offset

Analog input offset. Applied when used as current/
velocity reference.

Range: -10.000…10.000

85

AnalogOutFunction

Analog output function

0 = Not assigned
1 = Phase current (rms)
2 = Phase current (peak value)
3 = Motor velocity
4 = Phase current R
5 = Phase current S
6 = Phase current T
7 = Iq current
8 = Id current

86

AnalogOutVelocityScale

Analog output scale for velocity quantities

Range: 0…10 mV/rpm

29

EnableSwitchType

Enable switch function

0 = Inhibit only
1 = Enable as soon as asserted

ID

Parameter Name

Description

Value

266

Drive Mode

Set to Analog Current

5

35

CurrentScale

Current scale

Range: - X…+X Amps/Volt
X = drive peak output current/10

89

AnalogInput1Deadband

Analog input dead-band. Applied when used as a
velocity reference.

Range: 0…100 mV

90

AnalogInput1Offset

Analog input offset. Applied when used as current/
velocity reference.

Range: -10,000…10,000

85

AnalogOutFunction

Analog output function

0 = Not assigned
1 = Phase current (rms)
2 = Phase current (peak value)
3 = Motor velocity
4 = Phase current R
5 = Phase current S
6 = Phase current T
7 = Iq current
8 = Id current

87

AnalogOutCurrentScale

Analog output scale for current related quantities.

Range: 0…10V/A

29

EnableSwitchType

Enable switch function

0 = Inhibit only
1 = Enable as soon as asserted