Use the information in this section when designing your enclosure and planning
to mount your system components on the panel.

For on-line product selection and system configuration tools, including
AutoCAD (DXF) drawings of the product, see

http://www.ab.com/e-tools

.

System Mounting Requirements

To comply with UL and CE requirements, the Kinetix 300 system must be

enclosed in a grounded conductive enclosure offering protection as
defined in standard EN 60529 (IEC 529) to IP4X such that they are not
accessible to an operator or unskilled person. A NEMA 4X enclosure
exceeds these requirements providing protection to IP66.

The panel you install inside the enclosure for mounting your system

components must be on a flat, rigid, vertical surface that won’t be subjected
to shock, vibration, moisture, oil mist, dust, or corrosive vapors.

Size the drive enclosure so as not to exceed the maximum ambient

temperature rating. Consider heat dissipation specifications for all drive
components.

Segregate input power wiring and motor power cables from control wiring

and motor feedback cables. Use shielded cable for power wiring and
provide a grounded 360° clamp termination.

Use high-frequency (HF) bonding techniques to connect the enclosure,

machine frame, and motor housing, and to provide a low-impedance
return path for high-frequency (HF) energy and reduce electrical noise.

Use 2090 series motor feedback cables or use connector kits and properly
terminate the feedback cable shield. Drive-to-motor power and feedback
cables must not exceed 20 m (65.6 ft).

See the System Design for Control of Electrical Noise Reference Manual,
publication

GMC-RM001

, to better understand the concept of electrical noise

reduction.

IMPORTANT

System performance was tested at these cable length specifications. These
limitations are also a CE requirement.