Chapter 4

Connecting the Kinetix 300 Drive System

This example illustrates grounded three-phase power wired to single-phase
Kinetix 300 drives when phase-to-phase voltage exceed

s drive specifications.

A neutral must be connected when single-phase drives are attached to a three-
phase isolating transformer secondary. It is not necessary that all three-phases be
loaded with drives, but each drive must have its power return via the neutral
connection.

Figure 37 - Single-phase Amplifiers (one AC line filter per drive)

Feeder and branch short circuit protection is not illustrated.

If a three-phase line filter is used to feed multiple single-phase drives (not
recommended), it is important that the filter include a neutral connection as
shown above. This applies if three-phase is brought directly into the filter and no
isolating transformer is present.

ATTENTION: Failure to connect the neutral can result in supply voltage swings
at the individual drives. This occurs when the neutral point moves vectorially as
a result of load variations normally experienced by the individual drives. The
supply voltage swing may cause undervoltage and overvoltage trips on the
drives, and the drive can be damaged if the overvoltage limit is exceeded.

L1

L2

L3

L1

L2

L1

L2

L1

L2

IPD

L1

N

IPD

L1

N

IPD

L1

N

L1

L2

L1

L2

L1

L2

E

E

E

2097-V31PRx

IPD

L1
L2

IPD

L1
L2

IPD

L1
L2

2097-V33PRx

Bonded Cabinet Ground Bus

Transformer (WYE) Secondary

Ground Grid or Power Distribution Ground

AC Line

Filter

AC Line

Filter

AC Line

Filter

Kinetix 300 Drives

(System A)

Single-phase AC Input

Grounded

Neutral

Grounded Neutral

Kinetix 300 Drives

(System A)

Single-phase AC Input

Kinetix 300 Drives

(System A)

Single-phase AC Input

M1

Contactor

Input Fusing

IMPORTANT

Providing an EMC line filter for each drive is the preferred configuration, and
required for CE compliance.