Chapter 4

Connecting the Kinetix 300 Drive System

Ethernet Cable Connections

This procedure assumes you have your Logix Ethernet/IP module and
Kinetix 300 drive mounted and ready to connect the network cables.

The EtherNet/IP network is connected by using the Port 1 connector. See

page 36

to locate the Ethernet connector on your Kinetix 300 drive. See the

figure below to locate the connector on your Logix communication module.

Shielded Ethernet cable is available in lengths up to 78 m (256 ft). However, the
total length of Ethernet cable connecting drive-to-drive, drive-to-controller, or
drive-to-switch must not exceed 100 m (328 ft).

If the entire channel is constructed of stranded cable (no fixed cable), then this is
the equation for calculating maximum length:

Maximum Length = (113-2N)/y, meters
where N = the number of connections in the channel
and y = the loss factor compared to fixed cable (typically 1.2…1.5).

Figure 49 - CompactLogix Ethernet Port Location

The Port 1 Ethernet connection is used for connecting to a web browser and
configuring your Logix module.

Figure 50 - Ethernet Wiring Example - External Switch

CompactLogix

L23E

Ethernet Port

CompactLogix Controller Platform
1769-L23E-QB1B Shown

CompactLogix

L23E

00

300

00

300

CompactLogix Controller Platform

1769-L23E-QB1B Shown

Personal Computer

1783-EMS08T

Stratix 6000

Switch

Kinetix 300 Drives