Description of Operation

The safe torque-off feature provides a method, with sufficiently low probability
of failure on demand, to force the power-transistor control signals to a disabled
state. When disabled, or any time power is removed from the safety enable inputs,
all of the drives output-power transistors are released from the ON state,
effectively removing motive power generated by the drive. This results in a
condition where the motor is in a coasting condition (stop category 0). Disabling
the power transistor output does not provide mechanical isolation of the
electrical output, which may be required for some applications.

Under normal drive operation, the safe torque-off switches are energized. If either
of the safety enable inputs are de-energized, the gate control circuit is disabled. To
meet ISO 13849-1 (PLd) both safety channels must be used and monitored.

Functional Proof Tests

The functional safety standards require that functional proof tests be performed
on the equipment used in the system. Proof tests are performed at user-defined
intervals, not to exceed one year, and are dependent upon PFD and PFH values.

To proof test the safe torque-off function, you must interrupt power to the inputs
of the safe torque-off function at pins STO-4 and STO-6 and verify that the
drive is in the disabled state.

Proof Test Truth Table

Normal operation of the safe torque-off function, if monitored and verified,
constitutes the proof test. A safe torque-off mismatch results in error code E39.

ATTENTION: Permanent magnet motors may, in the event of two simultaneous
faults in the IGBT circuit, result in a rotation of up to 180 electrical degrees.

IMPORTANT

Users specific applications determine the time frame for the proof test interval,
but it must not exceed one year due to the use of switches internal to the drive,
as required by ISO 13849-1.

Safety Function State

Safety Input 1
(STO-4)

Safety Input 2
(STO-6)

Safety Status
Output (STO-3)

Drive Status
Indication

(1)

(1) Drive display changes to condition shown on enable of the drive (IN_ A3 Enable).

Normal operation

Energized

Energized

Energized

Run

Safe torque-off mismatch

Energized

De-energized

Energized

E39

De-energized

Energized

Energized

E39

Safe torque-off function
engaged

De-energized

De-energized

De-energized

E39