Rockwell Automation Publication 2097-UM001D-EN-P - November 2012

Chapter 2

Installing the Kinetix 300 Drive System

Figure 6 - Noise Zones (Bulletin 2097 AC line filters)

(1) If drive system I/O cable contains (dirty) relay wires, route cable in dirty wireway.
(2) For tight spaces use a grounded steel shield. For examples, see the System Design for Control of Electrical Noise Reference Manual,

publication

GMC-RM001

.

(3) This is a clean 24V DC available for any device that may require it. The 24V enters the clean wireway and exits to the left.
(4) This is a dirty 24V DC available for motor brakes and contactors. The 24V enters the dirty wireway and exits to the right.

Clean Wireway

24V Motor

Brake PS

Circuit

Breaker

Contactors

Kinetix 300

Drive

I/O

(1)

, Ethernet, and Feedback Cables

Very Dirty Zone

Segregated (not in wireway)

Route 24V DC I/O

Shielded Cable

Ethernet
(shielded)
Cable

I/O

(1)

, Motor Power, and Safety Cables

(4)

(3)

Dirty Wireway

XFMR

DC

Filter

Route encoder/analog/registration
shielded cables.

D

D

VD

VD

D

C

C

Bulletin 2097 AC line filters

mount to side, as shown, or

behind the drive.

No sensitive equipment

within 150 mm (6.0 in.).

(2)