Overtravel hardware inputs – Rockwell Automation 2097-Vxxx Kinetix 300 EtherNet/IP Indexing Servo Drive User Manual User Manual

Page 218

Advertising
background image

218

Rockwell Automation Publication 2097-UM001D-EN-P - November 2012

Appendix E

Overtravel Inputs

Overtravel Hardware Inputs

Overtravel inputs are dedicated inputs and cannot be used for anything else.

Table 83 - Overtravel Pin Assignments

The overtravel inputs are edge triggered and once the overtravel limit is exceeded,
the drive will perform the configured shutdown. Overtravel checking is
configured via MotionView software under DriveIP >IO > Digital IO > Hard
Limit Switches Action.

Overtravel inputs can be programed for normally open or normally closed
operation. Use EtherNet/IP Explicit Messaging tag ID 668 to modify this
parameter.

Figure 108 - Overtravel Configuration in MotionView Software

The default action is Not Assigned. These actions are configured via the pull-
down menu:

Disable and Coast - immediately disables the drive upon detecting an

overtravel condition. Disable and Coast is the only stopping action
available when overtravel is tripped in Analog Velocity Mode.

Decel and Disable - uses the Abort Decel rate to stop the servo and then

disable the drive. Decel and Disable is not available for Analog Velocity
Mode.

IOD Pin

Description

Signal

IOD-28

Positive overtravel input

IN_A2

IOD-27

Negative overtravel input

IN_A1

Advertising