Configure and Start Up the Kinetix 300 Drive

Chapter 6

Change the Encoder Resolution for an Incremental Encoder

The encoder resolution defaults to 5 μm per encoder count. If you must change
the resolution, do this.

1. Run the MotionView software.
2. From the Drive Organizer, click Motor.
3. Click Change Motor.
4. Click Custom Motor.
5. Click Create Custom.
6. Create a Vendor Name.

7. Create a Motor Model.

8. Enter either the Resolution (x1) or the Resolution (x4) value.
9. Click Save File.

10. Enter <filename>.cmt.xml.
11. Click Update Drive.

This important message appears.

12. Answer yes or no according to your motor needs.

This important message appears.

EXAMPLE

AB Custom

EXAMPLE

LDC-c030100DHT1u

IMPORTANT

We recommended you do auto-phasing when commissioning new
motors and wiring.