Userdefineddatalink, Drive enable – Rockwell Automation 2097-Vxxx Kinetix 300 EtherNet/IP Indexing Servo Drive User Manual User Manual

Page 158

Advertising
background image

158

Rockwell Automation Publication 2097-UM001D-EN-P - November 2012

Chapter 7

Troubleshooting the Kinetix 300 Drive System

UserDefinedDataLink

Drive parameters used in the

Explicit Messaging

section can be mapped into the

integer UserDefinedDataLink by using MotionView software. Then the
parameter can be toggled by using the UserDefinedIntegerData0 or
UserDefinedIntegerData1 tags within RSLogix 5000 software.

Figure 77 - UserDefinedDataLink Example Using Parameter 53

Drive Enable

The drive clears runtime faults if the drive enable command from RSLogix 5000
software is cycled and the fault reset in the MotionView software is configured
for On Disable. For the drive to be enabled, the DriveEn bit in the Output
Assembly needs to be set to 1. By changing that from 1 back to 0, the fault clears
as the drive disables.

Advertising