Equation 14, N equation 14, G equation 14 – Basler Electric BE1-11t User Manual

Page 108: Nd equation 15

Advertising
background image

96

9424200995 Rev H

The pickup settings in Times Tap can be related to primary amps by Equation 15. Minpu is the minimum
pickup setting in Times Tap. The definitions for the remaining variables in Equation 15 are the same as
those for Equation 13.

𝑋 =

𝑇𝐴𝑃𝑛

𝑙

𝑇𝐴𝑃𝑛

𝐴

=

𝑀𝑉𝐴 Γ— 1000 Γ— 𝐢𝑂𝑀𝑃𝑛

𝑇𝐴𝑃𝑛

𝐴

Γ— √3 Γ— 𝐾𝑉𝑛 Γ— 𝐢𝑇𝑅𝑛

Equation 14. Tap Adjustment Equation

πΌπ‘π‘Ÿπ‘– =

𝑀𝑖𝑛𝑝𝑒 Γ— 𝑇𝐴𝑃𝑛 Γ— 𝐢𝑇𝑅𝑛

𝐢𝑂𝑀𝑃𝑛

Equation 15. Calculate Primary Amps

% of Maximum - The maximum of the compensated input currents is used. For example, the restraint
current for phase A would be

I

RA

= max (I

AXCOMPS

)

where x = 2 for two current inputs.

% of Average - The average of the compensated input currents is used. For example, the restraint
current for phase A would be given by Equation 16.

𝐼

𝑅𝐴

=

π‘†π‘’π‘š π‘œπ‘“ 𝐼

𝐴π‘₯𝐢𝑂𝑀𝑃𝑆

π‘π‘’π‘šπ‘π‘’π‘Ÿ π‘œπ‘“ 𝐼𝑛𝑝𝑒𝑑𝑠

Equation 16. Calculate Restraint Current for Phase A, % of Average

Phase current differential element operational settings are configured on the Phase Current Differential
(87) settings screen (Figure 63) in BESTCOMSPlus. A legend for the chart (Figure 64) is shown by
clicking the Help button on this screen. Setting ranges and defaults are summarized in Table 35.

Figure 63. Phase Current Differential Settings Screen

0BPhase Current Differential (87) Protection