Alarm settings, User programmable alarms – Basler Electric BE1-11t User Manual

Page 171

Advertising
background image

9424200995 Rev H

159

Name

Description

RTD Out of Range

Remote Module 1 or 2 Alarm

S Demand

Apparent power (VA) demand maximum exceeded

Setting Change

Setting change made by user

Settings Group 0

Setting group 0 is active

Settings Group 1

Setting group 1 is active

Settings Group 2

Setting group 2 is active

Settings Group 3

Setting group 3 is active

SGC Active

Active setting group changed

SGC Logic Override

Setting group control was overridden by logic

Trip Coil Monitor

Monitored trip circuit open

uP Reset Alarm

Microprocessor watchdog circuit timed out

Var Negative Demand

Negative var demand maximum exceeded

Var Positive Demand

Positive var demand maximum exceeded

Watt Forward Demand

Forward watt demand maximum exceeded

Watt Reverse Demand

Reverse watt demand maximum exceeded

Alarm Settings

BESTCOMSPlus Navigation Path: Settings Explorer, Alarm Configuration, Alarms

HMI Navigation Path: Not available through the front panel

Alarms are enabled using BESTCOMSPlus. Use the Settings Explorer to open the Alarm Configuration,
Alarms tree branch. Configure alarms by selecting Disabled, Latching, or Non-Latching from the Minor,
Major, and Logic drop-down menus next to the alarms. Refer to Figure 115.

Figure 115. Alarm Settings Screen

User Programmable Alarms

BESTCOMSPlus Navigation Path: Settings Explorer, Alarm Configuration, User Programmable Alarms

HMI Navigation Path: Not available through the front panel

BE1-11t

Alarms