Power, Demand power reporting settings, Retrieving demand reporting information – Basler Electric BE1-11t User Manual

Page 184

Advertising
background image

172

9424200995 Rev H

Setting

Range

Increment

Unit of

Measure

Default

Phase Current Threshold

0 or 0.5 to 16

0.01

amps

0

Neutral/Ground Current Threshold

0 or 0.5 to 16

0.01

amps

0

Negative-Sequence Current
Threshold

0 or 0.5 to 16

0.01

amps

0

Power

Demand values are continuously calculated for real power (A kW, B kW, C kW, Total kW), reactive power
(A var, B var, C var, Total var), and apparent power (A VA, B VA, C VA, Total VA).

Demand Power Reporting Settings

BESTCOMSPlus Navigation Path: Settings Explorer, Alarm Configuration, Demands

HMI Navigation Path: Settings Explorer, Alarm Configuration, Demands

Settings are made using BESTCOMSPlus. Use the Settings Explorer to open the Alarm Configuration,
Demands tree branch. Demand settings for real power thresholds include Forward Watt and Reverse
Watt. Demand settings for reactive power include Forward Var and Reverse Var. A setting for apparent
power threshold is also provided. The demand power interval is defined by the Phase Interval setting.
Enter the appropriate demand power reporting settings. Refer to Figure 126.

Table 66 summarizes the demand power reporting settings.

Table 66. Demand Power Reporting Settings

Setting

Range

Increment

Unit of Measure

Default

Forward Watt Threshold

0 or 1 to 8,500

varies

watts

0

Reverse Watt Threshold

0 or 1 to 8,500

varies

watts

0

Forward var Threshold

0 or 1 to 8,500

varies

vars

0

Reverse var Threshold

0 or 1 to 8,500

varies

vars

0

VA Threshold

0 or 1 to 8,500

varies

VA

0

Retrieving Demand Reporting Information

BESTCOMSPlus Navigation Path: Metering Explorer, Demand

HMI Navigation Path: Metering Explorer, Demand Meter

Values and timestamps in the demand registers are reported in primary values. They can be read at the
front-panel display, through BESTCOMSPlus, and through the web page interface.

Peak demand values can be preset by pressing the Edit key and changing the value. Write access to the
Reports functional area is required to preset values at the front panel.

To access demand data through BESTCOMSPlus, use the Metering Explorer to open the Demand tree
branch and select Demand Current (Figure 127), Demand Power (Figure 128), Demand Reactive Power,
or Demand Apparent Power. The Demand Reactive Power and Demand Apparent Power screens are
similar.