Pickup verification (3i0 mode) – Basler Electric BE1-11t User Manual

Page 377

Advertising
background image

9424200995 Rev H

365

Table 157. Timing Test Settings (Phase Mode)

Pickup Setting

Time Delay

0.5 A

2,000 ms

0.5 A

5,000 ms

0.5 A

10,000 ms

Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 157. Record the

results.

Step 6: (Optional.) Repeat steps 1 through 5 for the B-phase and C-phase current inputs.

Step 7: (Optional.) Repeat steps 1 through 6 for settings group 1, 2, and 3.

Step 8: (Optional.) Repeat steps 1 through 7 for 50-2, 50-3, 50-4, 50-5, 50-6, 50-7, 50-8, and 50-9.

Step 9: (Optional.) Repeat steps 1 through 8 with CT Circuit 2 as the source. In step 3, replace D1 with

F1, D2 with F2, etc.

Pickup Verification (3I0 Mode)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 158 to the BE1-11t. Reset all

targets.

Table 158. Operational Settings (3I0 Mode)

Setting

Value

BESTCOMSPlus Screen

Description

Phase CT
Ratio

1

System Parameters, Sensing
Transformers

Sets phase CT ratio to 1

Element
Mode

3I0

Protection, Current,
Instantaneous Overcurrent (50-1)

Enables 50-1 function for 3I0 mode

Source

CT Circuit 1

Protection, Current,
Instantaneous Overcurrent (50-1)

Selects CT circuit 1 as the source

50-1
Residual

Enabled

Target Configuration, Targets

Enables residual target for 50-1

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 255.

Blocking is disabled.

OUT1 closes for 50-1 Trip.

OUT2 closes for 50-1 Pickup.

Fault recording is enabled.

Step 3: Use BESTCOMSPlus to open the Protection, Current, Instantaneous Overcurrent (50-1) screen

and send the low range test settings (minimum pickup setting) to the BE1-11t for your sensing
input type in Table 159.

BE1-11t

Instantaneous Overcurrent (50) Test

Advertising