Een (figure 41), N table 14 – Basler Electric BE1-11t User Manual

Page 62

Advertising
background image

50

9424200995 Rev H

Figure 41. Auxiliary Undervoltage Settings Screen

Table 14. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

*

Disabled,

3V0, V1, V2,

Vx Fundamental,

Vx Third Harmonic

n/a

n/a

Disabled

Pickup

0 or 1 to 150

0.1

volts

0

Inhibit Level

0 or 1 to 150

0.1

volts

0

Timing Mode

Definite or Inverse

n/a

n/a

Definite

Time Delay (Definite Timing)

50 to 600,000

varies

milliseconds

50

Time Dial (Inverse Timing)

0 to 9.9

0.1

units

0

* To use 3V0, V1, or V2, the VTP connection cannot be single-phase.

Auxiliary Undervoltage (27X) Protection