Basler Electric BE1-11t User Manual

Page 416

Advertising
background image

404

9424200995 Rev H

Setting

Value

BESTCOMSPlus Screen

Description

CT 2 Connection

WYE

System Parameters, Sensing
Transformers

Sets the CT 2 connection
to WYE

Phase VT Ratio

1

System Parameters, Sensing
Transformers

Sets phase VT ratio to 1

Phase VT
Connection

4W-Y

System Parameters, Sensing
Transformers

Sets phase VT connection
to 4W-Y

27/59 Mode

PN

System Parameters, Sensing
Transformers

Sets 27/59 mode to phase-
neutral

Circuit 1
Transformer
Connection

WYE

System Parameters, Transformer
Setup

Configures the primary side
for a WYE connection

Circuit 1 Ground
Compensation

No

System Parameters, Transformer
Setup

Disables the primary
winding zero sequence trap

(Optional) Circuit
1 Diff. Circuit

Primary

System Parameters, Transformer
Setup

Establishes circuit 1 on the
primary side of the
transformer. For report
labeling purposes only.

Circuit 1 Polarity

Normal

System Parameters, Transformer
Setup

Sets the phase rotation of
circuit 1 for ABC

Circuit 1 Phase
Relationship

A

System Parameters, Transformer
Setup

Sets A-phase in circuit 1
equal to the phase
relationship setting for
circuit 2

Circuit 2
Transformer
Connection

WYE

System Parameters, Transformer
Setup

Configures the secondary
side for a WYE connection

Circuit 2 Ground
Compensation

No

System Parameters, Transformer
Setup

Disables the secondary
winding zero sequence trap

(Optional) Circuit
2 Diff. Circuit

Secondary

System Parameters, Transformer
Setup

Establishes circuit 2 on the
secondary side of the
transformer. For report
labeling purposes only.

Circuit 2 Polarity

Normal

System Parameters, Transformer
Setup

Sets the phase rotation of
circuit 2 for ABC

Circuit 2 Phase
Relationship

A

System Parameters, Transformer
Setup

Sets A-phase in circuit 2
equal to the phase
relationship setting for
circuit 1

(Optional) IEC
Setup Winding 1

Wye
Primary

System Parameters, Transformer
Setup, IEC Transformer Setup

Configures the primary side
for a WYE connection

(Optional) IEC
Setup Winding 2

y0
Secondary

System Parameters, Transformer
Setup, IEC Transformer Setup

Configures the secondary
side for a WYE connection
with normal ABC phase
rotation

Circuit 1 Tap

2.00

System Parameters, Transformer
Setup

Sets the tap for circuit 1 to
2.00 A secondary

Circuit 2 Tap

2.00

System Parameters, Transformer
Setup

Sets the tap for circuit 2 to
2.00 A secondary

Phase Current Differential (87) Test

BE1-11t