Programming example – Basler Electric BE1-11t User Manual

Page 27

Advertising
background image

9424200995 Rev H

15

Figure 10. System Summary Screen

Programming Example

Changing default logic is sometimes required to match the protection requirements of the system.
Additionally, elements must be enabled and operating settings set. This example demonstrates how to
configure typical nominal settings and program the 50-3 instantaneous overcurrent element. System
nominal quantities are set to 69.3 volts and 3.6 amps. The 50-3 element is set for a 5.62 amp pickup and
a 30 second time delay. Additionally, the element pickup output is logically wired to output 4 and a user
alarm.

Step 1: Start BESTCOMSPlus and select New Connection, BE1-11 from the Communication pull-down

menu to connect to the BE1-11t. See Figure 6.

Step 2: The BE1-11 Connection screen appears. See Figure 7. Select USB Connection and click

Connect.

Step 3: Select Download Settings and Logic from Device from the Communication pull-down menu. This

copies all settings and logic from the BE1-11t to BESTCOMSPlus.

Step 4: Click on the View drop-down button and de-select Show Metering Panel and Show Setting

Information. See Figure 9. This maximizes the workspace.

Step 5: In the Settings Explorer, click the “+” next to BE1-11. This expands the sub menus in the tree.

Now expand System Parameters and select the Power System screen. See Figure 11.

Step 6: Under Nominal Settings, enter settings for Secondary Phase Voltage (69.3 V) and Secondary

Phase Current (3.6 A).

Step 7: In the Settings Explorer, expand Protection, Current and select the Instantaneous Overcurrent

(50-3) screen. See Figure 12.

Step 8: Select the Mode (3 Phase) and enter settings for Pickup (5.62 A) and Time Delay (30,000 ms).

BE1-11t

Quick Start

Advertising