Functional test report, Pickup verification (phase mode) – Basler Electric BE1-11t User Manual

Page 400

Advertising
background image

388

9424200995 Rev H

Table 185. Timing Test Settings (IG Mode)

Sensing

Type

Time

Dial

Applied
Current

5 A

0.5

1.00 A

2.50 A

12.50 A

5.0

1.00 A

2.50 A

12.50 A

9.9

1.00 A

2.50 A

12.50 A

1 A

0.5

0.20 A

0.50 A

2.50 A

5.0

0.20 A

0.50 A

2.50 A

9.9

0.20 A

0.50 A

2.50 A

SEF

0.5

0.20 A

0.50 A

0.80 A

5.0

0.20 A

0.50 A

0.80 A

9.9

0.20 A

0.50 A

0.80 A

Functional Test Report

Pickup Verification (Phase Mode)

Pickup Setting Range = 0.5 to 16 A for 5A sensing

0.1 to 3.2 A for 1A sensing

Pickup Accuracy =

±2% or ±50 mA, whichever is greater for 5A sensing

±2% or ±10 mA, whichever is greater for 1A sensing

Inverse Overcurrent (51) Test