Table 208. Characteristic Curve Cross-Reference

Curve

Curve Name

Similar To

S1

CO Short Inverse

ABB CO-2

S2

IAC Short Inverse

GE IAC-55

A

Standard Inverse

Refer to BS 142

A1

IEC Inverse

Refer to IEC 60255-151 Ed. 1

I1

CO Inverse Time

ABB CO-8

I2

IAC Inverse Time

GE IAC-51

M

CO Moderately Inverse

ABB CO-7

D1

IEEE Moderately Inverse

Refer to IEC 60255-151 Ed. 1

L1

CO Long Inverse

ABB CO-5

L2

IAC Long Inverse

GE IAC-66

G

Long Time Inverse (I

2

t)

Refer to BS 142

V1

CO Very Inverse

ABB CO-9

V2

IAC Very Inverse

GE IAC-53

B

Very Inverse (I

2

t)

Refer to BS 142

B1

IEC Very Inverse

Refer to IEC 60255-151 Ed. 1

E3

IEEE Very Inverse

Refer to IEC 60255-151 Ed. 1

E1

CO Extremely Inverse

ABB CO-11

E2

IAC Extremely Inverse

GE IAC-77

C

Extremely Inverse (I

2

t)

Refer to BS 142

C1

IEC Extremely Inverse

Refer to IEC 60255-151 Ed. 1

F1

IEEE Extremely Inverse

Refer to IEC 60255-151 Ed. 1

D

CO Definite Time

ABB CO-6

F

Fixed Time

n/a

46

K Factor

n/a

P

User Programmable

n/a

T1, T2, T3, T4

User Tables

n/a

Time Dial Setting Cross-Reference

Although the time characteristic curve shapes have been optimized for each BE1-11t, time dial settings of
Basler Electric protection systems are not identical to the settings of electromechanical induction disk
overcurrent relays. Table 209 helps you convert the time dial settings of induction disk relays to the
equivalent setting for Basler Electric protection systems. Enter time dial settings using BESTCOMSPlus.
For more information, refer to the

Inverse Overcurrent (51) Protection

chapter.

Using Table 209

Cross-reference table values were obtained by inspection of published electromechanical time current
characteristic curves. The time delay for a current of five times tap was entered into the time dial
calculator function for each time dial setting. The equivalent Basler Electric time dial setting was then
entered into the cross-reference table.

If your electromechanical relay time dial setting is between the values provided in the table, it will be
necessary to estimate the correct intermediate value between the electromechanical setting and the
Basler Electric setting.

BE1-11t

Time Curve Characteristics