Timing verification (3v0 mode), Pickup verification (v1 mode), Timing verification (v1 mode) – Basler Electric BE1-11t User Manual

Page 364: Pickup verification (v2 mode), Timing verification (v2 mode)

Advertising
background image

352

9424200995 Rev H

Timing Verification (3V0 Mode)

Time Delay Range = 50 to 600,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,968 ms

2,032 ms

P / F

5

5,000 ms

4,968 ms

5,032 ms

P / F

5

10,000 ms

9,950 ms

10,050 ms

P / F

Pickup Verification (V1 Mode)

Pickup Setting Range = 1 to 150 V

Pickup Accuracy =

±2% or ±1 V, whichever is greater

Dropout/Pickup Ratio = 98%

±1%

Step

Pickup

Setting

Low

Actual

Pickup

High

Low

*

Actual

Dropout

High

*

Pass/Fail

V1

VA

V1

VA

V1

VA

V1

VA

V1

VA

6

82.0 246.0 80.3 240.9

83.6 250.8 82.8 248.4

84.4 253.2

P / F

7

42.0 126.0 41.0 123.0

43.0 129.0 42.4 127.2

43.2 129.6

P / F

7

25.0

75.0

24.0

72.0

26.0

78.0

25.2

75.6

25.7

77.1

P / F

* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.

Timing Verification (V1 Mode)

Time Delay Range = 50 to 600,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,968 ms

2,032 ms

P / F

5

5,000 ms

4,968 ms

5,032 ms

P / F

5

10,000 ms

9,950 ms

10,050 ms

P / F

Pickup Verification (V2 Mode)

Pickup Setting Range = 1 to 150 V

Pickup Accuracy =

±2% or ±1 V, whichever is greater

Dropout/Pickup Ratio = 98%

±1%

Step

Pickup

Setting

Low

Actual

Pickup

High

Low

*

Actual

Dropout

High

*

Pass/Fail

V1

VA

V1

VA

V1

VA

V1

VA

V1

VA

6

82.0 246.0 80.3 240.9

83.6 250.8 82.8 248.4

84.4 253.2

P / F

7

42.0 126.0 41.0 123.0

43.0 129.0 42.4 127.2

43.2 129.6

P / F

7

25.0

75.0

24.0

72.0

26.0

78.0

25.2

75.6

25.7

77.1

P / F

* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.

Timing Verification (V2 Mode)

Time Delay Range = 50 to 600,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Auxiliary Overvoltage (59X) Test

BE1-11t