Retrieving oscillographic records, Distance to fault, O table 57 – Basler Electric BE1-11t User Manual

Page 164: N figure 112

Advertising
background image

152

9424200995 Rev H

Figure 112. Fault Records Screen

Table 57 summarizes the oscillographic records settings.

Table 57. Oscillographic Records Settings

Setting

Range

Increment

Default

Sample Resolution

32, 16, or 8

n/a

32

Number of Records to Store

32, 16, 8, or 4

n/a

32

Prefault Cycles

0 to 16

1

2

Retrieving Oscillographic Records

Oscillographic records can be downloaded through the Reports, Fault Reports screen in BESTCOMSPlus
(Figure 111). See Fault Reports earlier in this chapter. Oscillographic records can also be downloaded
through the web page interface. For more information, refer to the

BESTnetPlus

chapter.

Distance to Fault

The BE1-11t calculates distance to fault each time a fault record is triggered. Distance to fault is
calculated and displayed based on the power line parameters entered using BESTCOMSPlus or the front-
panel interface. Table 58 provides the power line operating settings.

Table 58. Power Line Operating Settings

Setting

Range

Increment

Unit of Measure

Default

Z1 Line Magnitude

0.05 to 200 (5A CTs)

0.01 to 40 (1A CTs)

varies

ohms

24

Z1 Line Angle

0 to 90

1

degrees

80

Z0 Line Magnitude

0.05 to 650 (5A CTs)
0.01 to 130 (1A CTs)

varies

ohms

8

Z0 Line Angle

0 to 90

1

degrees

80

Line Length

0.01 to 130

0.01

units

100

Line Length describes the power line parameters for which distance is to be computed over. The
parameters should be entered in units per line length with line length being the actual length of the power
line. Line length is entered as unit-less quantities and, therefore, can be entered in kilometers or miles.
Therefore, the distance results would be in whatever units the line length represented.

Using the Settings Explorer in BESTCOMSPlus, power line parameters can be entered on the System
Parameters, Power System screen. Settings are provided for Positive-Sequence Impedance, Zero-
Sequence Impedance, and Line Length. Refer to Figure 113.

Fault Reporting