Assuming a Vnom of 69.3 Vpn, 1 pu volts/hertz = (69.3

* √3) / 60 = 2.00. Using IEEE Std C37.102-2006 -

IEEE Guide for AC Generator Protection as a guide for setting overexcitation protection, the following
example demonstrates how to set the BE1-11t to provide a composite V/Hz characteristic for protection of
a generator and a step-up transformer:

Alarm = 105% @ 1 second time delay; V/Hz = 2

* 1.05 = 2.10

Inverse time pickup = 105%; Time Dial = 1.9; Inverse Trip Curve = (M-1)^2; V/Hz = 2

* 1.05 = 2.10

Definite Time #1 = 118% @ 6 seconds time delay; V/Hz = 1.18

* 2.0 = 2.36

The reset rate is determined by the Reset Dial setting. A setting of zero (0) gives an instantaneous reset.
Using the inverse squared characteristic, assume a trip time dial setting 2.0 and a pickup multiple of 1.2.
The total time to trip will be 50 seconds. If this exists for 30 seconds before being corrected (60% elapsed
time), what would the total reset time be for a reset dial setting of 5? Based on the reset equation
(Equation 5), the calculation will be:

seconds

300

100

50

30

0

.

5

T

100

FST

E

D

T

R

T

R

R

=

=

=

Equation 5. Time to Reset

If the overexcitation condition returns prior to total reset (i.e., less than 300 seconds), timing resumes from
that point at the inverse square rate. For example, if this condition recurs after 150 seconds or 50% of the
total reset time, then trip time from the second event will start at 30% instead of 0%, therefore tripping in
70% of the original trip time or 35 seconds. Figure 37 illustrates the inverse time delay and reset time.

Figure 37. Inverse Time Delay and Reset Time

Overexcitation (24) Protection