Timing verification (vx fundamental mode), N figure 248 – Basler Electric BE1-11t User Manual

Page 361

Advertising
background image

9424200995 Rev H

349

Figure 248. BESTlogicPlus Settings (Vx Fundamental Mode)

Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Overvoltage (59X-1) screen and send

the first row of test settings in Table 143 to the BE1-11t.

Table 143. Pickup Test Settings (Vx Fundamental Mode)

Pickup Setting

Time Delay

125 V

50 ms

75 V

50 ms

30 V

50 ms

Step 4: Prepare to monitor the 59X-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 248).

Step 5: Connect and apply a 120 Vac, single-phase voltage source to the Vx input, terminals C17

(polarity) and C18 (non-polarity).

Step 6: Slowly increase the voltage until OUT2 closes and record the pickup. Verify that there is a 59X-

1-AUX target on the front-panel display. Slowly decrease the voltage until OUT2 opens and
record the dropout. Reset the target.

Step 7: Verify the pickup and dropout accuracy at 70 Vac for a pickup setting of 75 V and 25 Vac for a

pickup setting of 30 V as listed in Table 143. Record the results.

Step 8: (Optional.) Repeat steps 1 through 7 for the B-phase and C-phase voltage inputs.

Step 9: (Optional.) Repeat steps 1 through 8 for settings group 1, 2, and 3.

Step 10: (Optional.) Repeat steps 1 through 9 for 59X-2, 59X-3, and 59X-4.

Timing Verification (Vx Fundamental Mode)

Step 1: Use BESTCOMSPlus to open the Protection, Voltage, Overvoltage (59X-1) screen and send

the first row of test settings in Table 144 to the BE1-11t for settings group 0.

Table 144. Timing Test Settings (Vx Fundamental Mode)

Pickup Setting

Time Delay

125 V

2,000 ms

125 V

5,000 ms

125 V

10,000 ms

Step 2: Prepare to monitor the 59X-1 timings. Timing accuracy is verified by measuring the elapsed

time between a sensing voltage change and OUT1 closing.

Step 3: Connect and apply a 120 Vac, single-phase voltage source to terminals C17 (polarity) and C18

(non-polarity).

Step 4: Step the voltage up to 130 volts. Measure the time delay and record the result.

BE1-11t