Pickup verification (ig mode), Timing verification (ig mode, 5a sensing), Timing verification (ig mode, 1a sensing) – Basler Electric BE1-11t User Manual

Page 404

Advertising
background image

392

9424200995 Rev H

Pickup Verification (IG Mode)

Pickup Setting Range = 0.5 to 16 A for 5A sensing

0.1 to 3.2 A for 1A sensing

0.01 to 0.8 A for SEF

Pickup Accuracy =

±2% or ±50 mA, whichever is greater for 5A sensing

±2% or ±10 mA, whichever is greater for 1A sensing

±2.5% or ±2.5 mA, whichever is greater for SEF

Dropout should occur between 93-99% of the actual pickup value.

Step

Pickup Setting

Low

Actual

Pickup

High

Low

*

Actual

Dropout

High

*

Pass/Fail

6

0.5 A (5A sensing)

0.45 A

0.55 A

0.465 A

0.495 A

P / F

7

5.0 A (5A sensing)

4.90 A

5.10 A

4.65 A

4.95 A

P / F

7

16.0 A (5A sensing)

15.68 A

16.32 A

14.88 A

15.84 A

P / F

6

0.1 A (1A sensing)

0.09 A

0.11 A

0.09 A

0.09 A

P / F

7

1.0 A (1A sensing)

0.98 A

1.02 A

0.93 A

0.99 A

P / F

7

3.2 A (1A sensing)

3.13 A

3.26 A

2.97 A

3.16 A

P / F

6

0.1 A (SEF sensing)

0.0075A

0.0125 A

0.0093 A

0.0099 A

P / F

7

0.5 A (SEF sensing)

0.317 A

0.682 A

0.465 A

0.495 A

P / F

7

0.8 A (SEF sensing)

0.63 A

0.97 A

0.074 A

0.792 A

P / F

* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.

Timing Verification (IG Mode, 5A Sensing)

Time Dial Range = 0.0 to 9.9

Timing Accuracy =

±5% or ±1½ cycles, whichever is greater

Step

Time Dial

Time Curve

Applied Current

Low

Actual Timing

High

Pass/Fail

4

0.5

I2

1.00 A

0.444 sec

0.491 sec

P / F

4

0.5

I2

2.50 A

0.190 sec

0.240 sec

P / F

4

0.5

I2

12.50 A

0.100 sec

0.150 sec

P / F

4

5.0

I2

1.00 A

4.204 sec

4.647 sec

P / F

4

5.0

I2

2.50 A

1.798 sec

1.988 sec

P / F

4

5.0

I2

12.50 A

0.944 sec

1.044 sec

P / F

4

9.9

I2

1.00 A

8.300 sec

9.173 sec

P / F

4

9.9

I2

2.50 A

3.535 sec

3.907 sec

P / F

4

9.9

I2

12.50 A

1.844 sec

2.038 sec

P / F

Timing Verification (IG Mode, 1A Sensing)

Time Dial Range = 0.0 to 9.9

Timing Accuracy =

±5% or ±1½ cycles, whichever is greater

Step

Time Dial

Time Curve

Applied Current

Low

Actual Timing

High

Pass/Fail

4

0.5

I2

0.20 A

0.444 sec

0.491 sec

P / F

4

0.5

I2

0.50 A

0.190 sec

0.240 sec

P / F

4

0.5

I2

2.50 A

0.100 sec

0.150 sec

P / F

4

5.0

I2

0.20 A

4.204 sec

4.647 sec

P / F

Inverse Overcurrent (51) Test

BE1-11t