Basler Electric BE1-11t User Manual

Page 145

Advertising
background image

9424200995 Rev H

133

Setting

Range

Purpose

Default

Monitor

Setting

Disable, IP, IG, I2,
3I0, 60FL

Determines when automatic setting group changes
occur. IP, IG, I2, or 3I0 can be selected so that setting
group changes are based on load current. Fuse Loss
(60FL) can also be used to switch setting groups. If 60FL
is entered as the Monitor Setting, the Switch Time,
Switch Threshold, Return Time, and Return Threshold
parameters are not required.

Disable

Setting

Group

Change

(SGC)

Alarm
Timer

0 = Disabled
1 - 10 seconds

Measured in seconds, the SGC alarm timer sets the
amount of time the alarm is on.

5

Logic Override of the Setting Group Selection Function

Setting group control can be overridden to allow manual setting group control.

BESTCOMSPlus Navigation Path: Metering Explorer, Control, Setting Group Control

HMI Navigation Path: Metering Explorer, Control, Settings Group Control

Use the Metering Explorer in BESTCOMSPlus to open the Control, Setting Group Control tree branch as
shown in Figure 94. Select a setting group to change to or return to logic control. The Active Setting
Group is also displayed on this screen.

Figure 94. Setting Group Control Screen

Manual setting group control can also be achieved by navigating to the Metering > Control > Settings
Group Control screen on the front-panel display.

BE1-11t

Setting Groups

Advertising