Een (figure 57), Table 30 – Basler Electric BE1-11t User Manual

Page 95

Advertising
background image

9424200995 Rev H

83

Figure 57. Inverse Overcurrent Settings Screen

Table 30. Operational Settings

Setting

Range

Increment

Unit of

Measure

Default

Mode

Disabled, IA, IB, IC, 3 Phase,

3I0, I1, I2, IG, or Unbalance

n/a

n/a

Disabled

Source

CT Circuit 1 or CT Circuit 2

n/a

n/a

CT Circuit 1

Pickup

0 or 0.5 to 16 (5A CTs)

0 or 0.1 to 3.2 (1A CTs)

0 or 0.01 to 0.8 (SEF)

varies

amps

0

2 to 100 (Unbalance mode)

1

percent

Time Dial

0 to 9.9

0 to 1 (IEC curves only)

0.0 to 99 (46 only)

varies

units

0

Curve

See the

Time Curve

Characteristics

chapter.

n/a

n/a

S1

Direction

Forward, Reverse, or Non-

Directional

n/a

n/a

Non-

Directional

Reset Timing

Integrating or Instantaneous

n/a

n/a

Instantaneous

A Coefficient

0 to 600

0.00001

A Coefficient

0.26630

B Coefficient

0 to 25

0.00001

B Coefficient

0.03393

BE1-11t

Inverse Overcurrent (51) Protection

Advertising