2nd harmonic restraint verification (independent), 2nd harmonic restraint verification (shared), 5th harmonic restraint verification (independent) – Basler Electric BE1-11t User Manual

Page 425: 5th harmonic restraint verification (shared)

Advertising
background image

9424200995 Rev H

413

2

nd

Harmonic Restraint Verification (Independent)

Pickup Accuracy =

±2% or ±0.05A, whichever is greater.

Step

Pickup Setting

Low

Actual Pickup

High

Pass/Fail

5

0.24 A

0.19 A

0.29 A

P / F

2

nd

Harmonic Restraint Verification (Shared)

Pickup Accuracy =

±2% or ±0.05A, whichever is greater.

Step

Pickup Setting

Low

Actual Pickup

High

Pass/Fail

5

3 x (0.08) A

3x (0.06) A

3 x (0.10) A

P / F

5

th

Harmonic Restraint Verification (Independent)

Pickup Accuracy =

±2% or ±0.05A, whichever is greater.

Step

Pickup Setting

Low

Actual Pickup

High

Pass/Fail

5

0.24 A

0.19 A

0.29 A

P / F

5

th

Harmonic Restraint Verification (Shared)

Pickup Accuracy =

±2% or ±0.05A, whichever is greater.

Step

Pickup Setting

Low

Actual Pickup

High

Pass/Fail

5

3 x (0.23) A

3x (0.22) A

3 x (0.25) A

P / F

BE1-11t

Phase Current Differential (87) Test