9424200995 Rev H

Minimum Restraint Pickup (I

op

)

Setting Range ........................................................... 0.1 to 1.00 per unit

2

nd

Slope Pickup (I

res

)

Setting Range ........................................................... 0.1 to 20.0 per unit

Restraint Slope 1
Setting Range ........................................................... 5 to 100%

Restraint Slope 2
Setting Range ........................................................... 15 to 140%

Time Delay
Setting Range ........................................................... 0 to 60,000 ms
Accuracy....................................................................

±0.5% or ±½ cycle, whichever is greater, plus trip

time for instantaneous response (0.0 setting)

*

* Trip Time for 0.0 Delay Setting .............................. 1¼ cycles maximum for currents ≥ 5 times the pickup

setting. 1¾ cycles maximum for a current of 2
times pickup. Two cycles maximum for a current
of 1.05 times the pickup setting.

87N - Neutral Current Differential Protection

Iop Minimum Pickup

5 Ampere CT

Setting Range ........................................................... 0.1 to 5 A
Accuracy....................................................................

±3% or ±75 mA, whichever is greater

1 Ampere CT

Setting Range ........................................................... 0.02 to 1 A
Accuracy.................................................................... 5 A CT:

±3% or ±15 mA, whichever

Overcorrection Coefficient
Setting Range ........................................................... 1 to 1.3

Time Delay
Setting Range ........................................................... 0 to 60,000 ms
Accuracy....................................................................

±0.5% or ±½ cycle, whichever is greater, plus trip

time for instantaneous response (0.0 setting)

*

* Trip Time for 0.0 Delay Setting .............................. 1¼ cycles maximum for currents ≥ 5 times the pickup

setting. 1¾ cycles maximum for a current of 2
times pickup. Two cycles maximum for a current
of 1.05 times the pickup setting.

Automatic Setting Group Characteristics

Number of Setting Groups ........................................ 4

Control Modes
Automatic .................................................................. Cold-Load Pickup, Dynamic Load or Unbalance
External ..................................................................... Discrete Input Logic, Binary Input Logic

Switch Threshold
Range ........................................................................ 0.1 to 25 A (5 A), 0.02 to 5 A (1 A)
Accuracy....................................................................

±2% or ±0.05 A (5 A), ±2% or ±0.01 A (1 A)

Specifications