Differential, Figure 99) – Basler Electric BE1-11t User Manual

Page 151

Advertising
background image

9424200995 Rev H

139

Figure 99. Analog Metering, Frequency Screen

Differential

The differential value is calculated as shown in the following equations:

If 87 Mode = Phase Differential and Slope Mode = Maximum, then IOP A = |𝐼

𝐢𝑂𝑀𝑃𝐴1

+ 𝐼

𝐢𝑂𝑀𝑃𝐴2

|

where: I

COMPA1

=

IA

1

TAP

1

and I

COMPA2

=

IA

2

TAP

2

Equation 19. IOP A Calculation when 87 Mode = Phase Differential

If 87 Mode = Phase Differential, then IR A = max (IRA

1

, IRA

2

)

Equation 20. IR A Calculation when 87 Mode = Phase Differential and Slope Mode = Maximum

If 87 Mode = Phase Differential and Slope Mode = Average, then IR A = avg (IRA

1

, IRA

2

)

Equation 21. IR A Calculation when 87 Mode = Phase Differential and Slope Mode = Average

Differential metering data is found in BESTCOMSPlus (Figure 100) and on the Metering > Analog
Metering > Differential screen of the front-panel display.

Figure 100. Analog Metering, Differential Screen

BE1-11t

Metering