Pickup verification (3i0 mode) – Basler Electric BE1-11t User Manual

Page 393

Advertising
background image

9424200995 Rev H

381

Step 2: Prepare to monitor the 51-1 timings. Timing accuracy is verified by measuring the elapsed time

between a sensing current change and OUT1 closing.

Step 3: Connect a current source to BE1-11t terminals D1 and D2 (A-phase).

Step 4: Using the values listed in Table 173, apply the appropriate current values, and measure the

time between the application of current and the closure of OUT1. Record the results.

Step 5: Repeat step 4 for all of the current and time dial settings for your current sensing type.

Step 6: (Optional.) Repeat steps 1 through 5 for the B-phase and C-phase current inputs. Note: Be sure

to enable proper target for each phase being tested.

Step 7: (Optional.) Repeat steps 1 through 6 for settings group 1, 2, and 3.

Step 8: (Optional.) Repeat steps 1 through 7 for 51-2, 51-3, 51-4, 51-5, 51-6, 51-7, 51-8, and 51-9.

Step 9: (Optional.) Repeat steps 1 through 8 with CT Circuit 2 as the source. In step 3, replace D1 with

F1, D2 with F2, etc.

Table 173. Timing Test Settings (Phase Mode)

Sensing Type

Time Dial

Applied Current

5 A

0.5

1.00 A

2.50 A

12.50 A

5.0

1.00 A

2.50 A

12.50 A

9.9

1.00 A

2.50 A

12.50 A

1 A

0.5

0.20 A

0.50 A

2.50 A

5.0

0.20 A

0.50 A

2.50 A

9.9

0.20 A

0.50 A

2.50 A

Pickup Verification (3I0 Mode)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 174 to the BE1-11t. Reset all

targets.

BE1-11t

Inverse Overcurrent (51) Test