9424200995 Rev H

353

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,968 ms

2,032 ms

P / F

5

5,000 ms

4,968 ms

5,032 ms

P / F

5

10,000 ms

9,950 ms

10,050 ms

P / F

Pickup Verification (Vx Fundamental Mode)

Pickup Setting Range = 1 to 150 V

Pickup Accuracy =

±2% or ±1 V, whichever is greater

Dropout/Pickup Ratio = 98%

±1%

Step Pickup Setting

Low

Actual Pickup

High

Low

*

Actual Dropout

High

*

Pass/Fail

6

125.0 V

122.5 V

127.5 V 121.3 V

123.8 V

P / F

7

75.0 V

73.5 V

76.6 V

72.8 V

74.3 V

P / F

7

30.0 V

29.0 V

31.0 V

29.1 V

29.7 V

P / F

* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.

Timing Verification (Vx Fundamental Mode)

Time Delay Range = 50 to 600,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,968 ms

2,032 ms

P / F

5

5,000 ms

4,968 ms

5,032 ms

P / F

5

10,000 ms

9,950 ms

10,050 ms

P / F

Pickup Verification (Vx Third Harmonic Mode)

Pickup Setting Range = 1 to 150 V

Pickup Accuracy =

±2% or ±1 V, whichever is greater

Dropout/Pickup Ratio = 98%

±1%

Step Pickup Setting

Low

Actual Pickup

High

Low

*

Actual Dropout

High

*

Pass/Fail

6

125.0 V

122.5 V

127.5 V 121.3 V

123.8 V

P / F

7

75.0 V

73.5 V

76.6 V

72.8 V

74.3 V

P / F

7

30.0 V

29.0 V

31.0 V

29.1 V

29.7 V

P / F

* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.

Timing Verification (Vx Third Harmonic Mode)

Time Delay Range = 50 to 600,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,968 ms

2,032 ms

P / F

5

5,000 ms

4,968 ms

5,032 ms

P / F

5

10,000 ms

9,950 ms

10,050 ms

P / F


BE1-11t

Auxiliary Overvoltage (59X) Test

Advertising