Unrestrained functional test procedure, Pickup verification, Harmonic restraint functional test procedure – Basler Electric BE1-11t User Manual

Page 422

Advertising
background image

410

9424200995 Rev H

Unrestrained Functional Test Procedure

Pickup Verification

Step 1: Use BESTCOMSPlus to verify the operational settings in Table 194 and logic in Figure 266.

Reset all targets.

Figure 266. BESTlogicPlus Settings (87U)

Step 2: Prepare to monitor the unrestrained 87 element. Operation can be verified by monitoring OUT1

(see Figure 266).

Step 3: Connect a single-phase current source to terminals D1 (A-phase polarity) and D2 (A-phase non-

polarity).

Step 4: Slowly increase the current magnitude until OUT1 closes and record the pickup. This should

occur at 4.0 A

±0.08 A. Verify that there is an 87 Unrestrained A target on the HMI screen.

Step 5: (Optional.) Repeat steps 1 through 4 for B-phase (terminals D3 and D4) and C-phase (terminals

D5 and D6).

Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.

Harmonic Restraint Functional Test Procedure

Second Harmonic Restraint Verification (Independent)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 193 and verify the logic in Figure

265. Reset all targets.

Step 2: Connect in parallel an A-phase current source of 50 or 60-hertz and a second A-phase current

source of twice the applied fundamental (100 or 120-hertz) to terminals D1 (A-phase polarity)
and D2 (A-phase non-polarity).

Step3:

Apply 2 amps at 0

° of the 50 or 60-hertz source. OUT2 should close immediately and OUT1

after the programmed time delay of 100 ms. Verify that there is an 87A target on the front-panel
display screen.

Step 4: Increase the second harmonic current source until OUT1 opens and record the magnitude of

the second harmonic source.

Step 5: To calculate the second-harmonic Restraint percentage, divide the second-harmonic current

measured in step 4 by the current applied in step 3. (Divide the harmonic current by the
fundamental current.). This should be 12% or 0.24 A

±0.05 A.

Step 6: (Optional.) Repeat steps 1 through 5 for the B-phase (terminals D3 and D4) and C-phase

(terminals D5 and D6) current inputs.

Step 7: (Optional.) Repeat steps 1 through 6 for settings group 1, 2, and 3.

Phase Current Differential (87) Test

BE1-11t

Advertising