Timing verification (vx fundamental mode), Pickup verification (vx third harmonic mode), Timing verification (vx third harmonic mode) – Basler Electric BE1-11t User Manual

Page 350

Advertising
background image

338

9424200995 Rev H

Timing Verification (Vx Fundamental Mode)

Time Delay Range = 50 to 600,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,968 ms

2,032 ms

P / F

5

5,000 ms

4,968 ms

5,032 ms

P / F

5

10,000 ms

9,950 ms

10,050 ms

P / F

Pickup Verification (Vx Third Harmonic Mode)

Pickup Setting Range = 1 to 150 V

Pickup Accuracy =

±2% or ±1 V, whichever is greater

Reset/Pickup Ratio = 102%

±1%

Step

Pickup Setting

Low

Actual Pickup

High

Low

*

Actual Reset

High

*

Pass/Fail

6

115.0 V

112.7 V

117.3 V

116.1 V

118.4 V

P / F

7

65.0 V

63.7 V

66.3 V

65.6 V

66.9 V

P / F

7

20.0 V

19.0 V

21.0 V

20.2 V

20.6 V

P / F

* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.

Timing Verification (Vx Third Harmonic Mode)

Time Delay Range = 50 to 600,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,968 ms

2,032 ms

P / F

5

5,000 ms

4,968 ms

5,032 ms

P / F

5

10,000 ms

9,950 ms

10,050 ms

P / F

Auxiliary Undervoltage (27X) Test

BE1-11t