Settings example, Een (figure 34), N table 9 – Basler Electric BE1-11t User Manual

Page 52

Advertising
background image

40

9424200995 Rev H

Figure 34. Overexcitation Settings Screen

Table 9. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Disabled or Enabled

n/a

n/a

Disabled

Pickup (Inverse Time)

0 or 0.5 to 6

0.01

v/Hz

0

Time Dial (Inverse Time)

0 to 9.9

0.1

units

0

Reset Dial (Inverse Time)

0 to 9.9

0.1

units

0

Curve Exponent (Inverse Time)

0.5, 1, or 2

n/a

n/a

1

Pickup (Definite Time 1 & 2)

0 or 0.5 to 6

0.01

v/Hz

0

Time Delay (Definite Time 1 & 2)

50 to 600,000

varies

milliseconds

50

Settings Example

The overexcitation element is used to de-energize a generator or transformer that is experiencing an
overexcitation condition. Therefore, the manufacturer's overexcitation limit curves are required to
establish optimum protection. Figure 35 and Figure 36 show examples of a transformer and generator
limit curve along with the optimum composite protection characteristic.

Note

Actual damage curves must be obtained from the equipment
manufacturer for the particular equipment to be protected.

Overexcitation (24) Protection

BE1-11t