N figure 270 – Basler Electric BE1-11t User Manual

Page 436

Advertising
background image

424

9424200995 Rev H

Figure 270. BESTlogicPlus Settings

Step 3: Steps 4 through 6 will initiate the 62-1 timer by changing the 43-1 switch state to ON (logic 1).

Once initiated, the 62-1 timer will force an output based on the 400 ms pickup time setting.

Step 4: Use the Metering Explorer of BESTCOMSPlus to open the Control, Virtual Switches tree branch

(Figure 271). Using select-before-operate, perform the following steps to control a virtual switch.

Figure 271. BESTCOMSPlus Virtual Switches Control Screen

Step 5: Click the 43-1 button to select it. Login may be required. The On or Off indicator (current state)

will begin to flash.

Note

If step 6 is not performed within 25 seconds of step 5, the indicator will
stop flashing and the 43-1 button will have to be selected again.

Step 6: Click on the 43-1 button a second time to operate it. After clicking Yes, the On or Off indicator

(previous state) will stop flashing and the On or Off indicator (current/new state) will light.

Step 7: Repeat steps 5 and 6 to change the state of the 43-1 switch to open and remove the initiate

input from the 62-1 timer.

Step 8: Use the Metering Explorer in BESTCOMSPlus to open the Reports, Sequence of Events

screen.

Step 9: Verify that the 43-1 switch change to an ON state was logged and approximately 400 ms later,

the 62-1 timer picked up. Then, sometime later, the 43-1 switch change to an OFF state was
logged and the 62-1 timer dropped out approximately 2,000 ms later. The state of the 43-1
switch in the SER report uses the programmable name parameters applied to the switch.
Figure 272 illustrates the timing relationship of the 43-1 switch and 62-1 timer.

Logic Timers (62) Test

BE1-11t