Bestlogic™plus, General specifications, Ac current inputs – Basler Electric BE1-11t User Manual

Page 463: Phase ac voltage inputs

Advertising
background image

9424200995 Rev H

451

Switch Time
Range ........................................................................ 0 to 60 min with 1 min increments where 0 =

disabled

Accuracy....................................................................

±0.5% or ±2 s, whichever is greater

BESTlogic

Plus

Update Rate .............................................................. ¼ cycle

General Specifications

AC Current Inputs

5 Ampere CT
Continuous Rating ..................................................... 20 A
One Second Rating ................................................... 400 A

For other current levels, use the formula: I= (K/t)

½

where t = time in seconds, K = 160,000.

Begins to Clip (Saturate) ........................................... 150 A
Burden ....................................................................... <10 m

1 Ampere CT
Continuous Rating ..................................................... 4 A
One Second Rating ................................................... 80 A

For other current levels, use the following formula: I = (K/t)

½

where t = time in seconds, K = 90,000.

Begins to Clip (Saturate) ........................................... 30 A
Burden ....................................................................... <10 m

SEF
Continuous Rating ..................................................... 4 A
One Second Rating ................................................... 80 A
Begins to Clip (Saturate) ........................................... 7.5 A
Burden ....................................................................... <22 m

Terminals (CT1)
IA1 ............................................................................. D1, D2
IB1 ............................................................................. D3, D4
IC1 ............................................................................. D5, D6
IN1 ............................................................................. D7, D8

Terminals (CT2)
IA2 ............................................................................. F1, F2
IB2 ............................................................................. F3, F4
IC2 ............................................................................. F5, F6
IN2 ............................................................................. F7, F8

Phase AC Voltage Inputs

Continuous Rating ..................................................... 300 V, Line to Line
One Second Rating ................................................... 600 V, Line to Neutral
Burden ....................................................................... <1 VA @ 300 Vac

Terminals
VA .............................................................................. C13
VB .............................................................................. C14
VC ............................................................................. C15
N ................................................................................ C16

BE1-11t

Specifications