Frequency (81) test, Functional test procedure, Overfrequency pickup verification – Basler Electric BE1-11t User Manual

Page 367

Advertising
background image

9424200995 Rev H

355

Frequency (81) Test

Functional testing is a way to assess this protection system’s suitability for your application. Functional
testing goes beyond the more basic tests found in acceptance testing, but lacks the detailed function
testing that is part of the commissioning process.

Test each of the following functions to verify that this BE1-11t measures accurately, is within specified
tolerances, and operates correctly. These tests are also suitable for assisting in systematic
troubleshooting in the event that an operation is questioned. Revisiting the test of a specific function can
help verify whether the BE1-11t is operating within specified tolerances. For further assistance, contact
Basler Electric, Technical Sales Support.

Refer to the

Terminals and Connectors

chapter for terminal locations and connections.

Reset all targets prior to each test by navigating to the Metering > Status > Targets screen and pressing
the front-panel Reset key. Enter the appropriate username and password if prompted. Clear all logic prior
to each test by using the Settings Explorer in BESTCOMSPlus

® to open the BESTlogic™Plus

Programmable Logic screen and click the Clear button located on the toolbar. After new BESTlogicPlus
settings are made, click the Save button located on the toolbar to compile BESTlogicPlus. Upload
BESTlogicPlus settings by selecting Upload Logic to Device from the Communication pull-down menu.
Operational settings can be sent by selecting Upload Settings to Device from the Communication pull-
down menu or by clicking the Send Settings button on the toolbar.

The actual operating time of an output contact is equal to the recognition time plus the time delay setting
(accuracy) plus 6 milliseconds. Output contact operating time depends upon the type of test set used and
its operating characteristics.

A Functional Test Report is included at the end of this chapter. It should be used to record the results and
verify pickup and timing accuracy.

Refer to the

Frequency (81) Protection

chapter for more information on this function.

Note

Testing the 81 Rate of Change (ROC) mode requires a voltage source
capable of smoothly sweeping the frequency of the applied voltage for
a variable positive and negative rate of change. Frequency step
changes at 1 millisecond intervals (maximum) are required to support
the accuracy requirement of the element.

Functional Test Procedure

Overfrequency Pickup Verification

Step 1: Use BESTCOMSPlus to send the operational settings in Table 148 to the BE1-11t. Reset all

targets.

Table 148. Operational Settings (Overfrequency)

Setting

Value

BESTCOMSPlus Screen

Description

Element Mode

Over

Protection, Frequency (81-1)

Enables 81-1 function for Over mode

Source

Phase VT

Protection, Frequency (81-1)

Sets source to Phase VT

Voltage Inhibit

40 V

Protection, Frequency (81-1)

Sets voltage inhibit pickup to 40 V

81-1 Over

Enabled

Target Configuration, Targets

Enables Over target for 81-1

BE1-11t

Frequency (81) Test