Underfrequency Pickup Verification

Pickup Setting Range = 15 to 70 Hz

Pickup Accuracy =

±0.01 Hz

Reset = 0.02 Hz

±0.01 Hz of the actual pickup value

Step

Pickup

Setting

Low

Actual

Pickup

High

Low

*

Actual

Dropout

High

*

Pass/Fail

6

42 Hz

41.99 Hz

42.01 Hz

41.97 Hz

41.99 Hz

P / F

7

46 Hz

45.99 Hz

46.01 Hz

45.97 Hz

45.99 Hz

P / F

7

48 Hz

47.99 Hz

48.01 Hz

47.97 Hz

47.99 Hz

P / F

* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.

Time Delay Verification

Time Delay Range = 0 to 600,000 ms

Timing Accuracy =

±0.5% or ±1 cycle, whichever is greater + 3 cycles recognition time for time delay

settings < 50 ms

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,983 ms

2,017 ms

P / F

5

5,000 ms

4,975 ms

5,025 ms

P / F

5

10,000 ms

9,950 ms

10,050 ms

P / F

Pickup Verification (ROC Frequency)

ROC Pickup Setting Range = 0.2 to 20 Hz/sec

Accuracy =

±2% or ±0.1 Hz/sec, whichever is greater

Step

Setting

Low

Pickup

High

Pass/Fail

8

10 Hz/sec

9.8 Hz/sec

10.2 Hz/sec

P / F

9

2 Hz/sec

1.9 Hz/sec

2.1 Hz/sec

P / F

BE1-11t

Frequency (81) Test