Pickup verification (roc frequency) – Basler Electric BE1-11t User Manual

Page 370

Advertising
background image

358

9424200995 Rev H

Step 3: Connect and apply a 120 Vac, 60-hertz voltage source to terminals C13 (A-phase) and C16

(neutral).

Step 4: Step the frequency of the applied voltage down to 55-hertz. Measure the time delay and record

the result.

Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delays listed in Table 152. Record the

results.

Step 6: (Optional.) Repeat steps 1 through 5 for settings groups 1, 2, and 3.

Step 7: (Optional.) Repeat steps 1 through 6 for 81-2, 81-3, 81-4, 81-5, 81-6, 81-7, and 81-8.

Pickup Verification (ROC Frequency)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 153 to the BE1-11t. Reset all

targets.

Table 153. Operational Settings (ROC Frequency)

Setting

Value

BESTCOMSPlus

Screen

Description

Element Mode

Rate of
Change

Protection, Frequency
(81-1)

Enables 81-1 function for Rate of
Change mode

Source

Phase VT

Protection, Frequency
(81-1)

Sets source to Phase VT

Pickup

10 Hz/sec

Protection, Frequency
(81-1)

Sets pickup to 10 Hz/sec

Voltage Inhibit

40 V

Protection, Frequency
(81-1)

Sets voltage inhibit pickup to 40 V

Over Frequency
Inhibit

64 Hz

Protection, Frequency
(81-1)

Sets over frequency inhibit to 64 Hz

Under Frequency
Inhibit

46 Hz

Protection, Frequency
(81-1)

Sets under frequency inhibit to 46
Hz

81-1 ROC

Enabled

Target Configuration,
Targets

Enables ROC target for 81-1

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 252.

Blocking is disabled.

OUT1 closes for 81-1 Trip.

OUT2 closes for 81-1 Pickup.

Fault recording is enabled.

Figure 252. BESTlogicPlus Settings (ROC Frequency)

Step 3: Prepare to monitor the 81-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 252).

Frequency (81) Test