Basler Electric BE1-11t User Manual

Page 173

Advertising
background image

9424200995 Rev H

161

Reset will reset all major alarms. The Minor Alarm Reset will reset all minor alarms. The Logic Alarm
Reset will reset all logic alarms. Use the drag-and-drop method to connect a variable or series of
variables to the Reset input. The alarm reset logic blocks are shown in Figure 118.

Figure 118. Alarm Reset Logic Block

Major and Minor alarms can be cleared by pressing the Reset button on the front-panel interface while the
Alarms screen is being displayed or through BESTCOMSPlus. Alarms cannot be reset through the web
page interface.

Pressing the front-panel Reset key clears the alarms and the Major Alarm or Minor Alarm LED.
Depending on device security setup, a username and password may be required to reset alarms at the
front panel. Logging in is not required if the Unsecured Access Level is set to Operator or higher, as long
as no other port has access higher than Read. Alarm reset can also be set outside of security control,
allowing reset without logging in. Refer to the

Security

chapter for more information.

An alarm reset is available as a status input in BESTlogicPlus. Refer to the

BESTlogicPlus

chapter for

more information.

BE1-11t

Alarms