Basler Electric BE1-11t User Manual

Page 330

Advertising
background image

318

9424200995 Rev H

Setting

Value

BESTCOMSPlus Screen

Description

Element Mode

Enabled

Protection, Voltage,
Overexcitation

Enables 24 function

24

Enabled

Target Configuration, Targets

Enables target for 24

24 Volts Per Hertz

Major/Non-
Latching

Alarm Configuration, Alarms

Enables alarm for 24

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 237.

Blocking is disabled.

OUT1 closes for 24 Trip.

OUT2 closes for 24 Pickup.

Figure 237. BESTlogicPlus Settings

Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Overexcitation (24) screen and send the

test settings in Table 106 to the BE1-11t.

Table 106. Alarm and Inverse Time Pickup Test Settings

Setting

Value

Description

Inverse Time Pickup

2.1

Sets Inverse Time Pickup at 1.05% of nominal (2.10 V/Hz)

Inverse Time Dial

0

Sets Inverse Time Dial at minimum

Inverse Reset Dial

0

Sets Inverse Reset Dial at minimum

Curve Exponent

2

Sets Curve Exponent to 2

Definite Timer 1 Pickup

0

Disables Definite Timer 1 Pickup

Definite Timer 2 Pickup

0

Disables Definite Timer 2 Pickup

Alarm Pickup

2.05

Sets Alarm at 1.025% of nominal (2.05 V/Hz)

Step 4: Prepare to monitor the operation of the 24 Alarm and Trip functions. Alarm operation can be

verified by monitoring the Major Alarm LED on the protection system's front panel. Operation of
the 24 Trip can be verified by monitoring OUT1.

Step 5: Connect a three-phase, 100 Vac/50-Hz or 120 Vac/60-hertz voltage source (depending on

user's nominal frequency) to Terminals C13 (A-phase), C14 (B-phase), C15 (C-phase), and
C16 (neutral).

Step 6: Apply A-phase voltage at nominal frequency and slowly increase until the Major Alarm LED

lights (V/H PU x Freq x % Alarm = PU) and record the alarm pickup. Slowly decrease the A-
phase voltage until the Major Alarm LED extinguishes and record the dropout.

Step 7: Apply A-phase voltage at nominal frequency and slowly increase until OUT2 closes (V/H Trip x

Freq = PU) and record the pickup. Verify that there is a 24 target on the front-panel display.
Slowly decrease the A-phase voltage until OUT2 opens and record the dropout.

Step 8: (Optional.) Repeat steps 1 through 7 for higher and lower alarm and pickup settings.

Step 9: (Optional.) Repeat steps 1 through 8 for frequencies other than nominal.

Overexcitation (24) Test

BE1-11t