Connection settings for current differential, Figure 231), N table 94 – Basler Electric BE1-11t User Manual

Page 300

Advertising
background image

288

9424200995 Rev H

Figure 231. Transformer Setup Screen

Table 94. Transformer Settings

Setting

Range

Increment

Unit

Default

Tap Calculation Mode

Manual or Automatic

n/a

n/a

Manual

MVA Rating

0.5 to 10,000

0.1

n/a

0.5

kV Rating

0.01 to 1,000

n/a

n/a

n/a

Tap

2 to 20 (5A CTs) or 0.4 to 4 (1A CTs)

0.01

n/a

2.00

CT Connection

Set on the Sensing Transformers screen

n/a

n/a

n/a

Phase CT Ratio

Set on the Sensing Transformers screen

n/a

n/a

n/a

Transformer Connection

WYE, DAB, DAC, ZAB, ZAC, or NA

n/a

n/a

WYE

Ground Connection

Yes or No

n/a

n/a

No

Differential Circuit

Primary, Secondary, or None

n/a

n/a

Primary

Polarity

Yes or No

n/a

n/a

No

Phase Relationship

A, B, or C

n/a

n/a

A

Connection Settings for Current Differential

When the zone of protection includes a transformer, it may be necessary to provide phase angle and zero
sequence compensation to the currents used by the Phase Current Differential Protection (87) element.
See Figure 232 and Figure 233. For each input circuit, a setting is provided to enter the transformer
connections associated with that input.

Configuration

BE1-11t

Advertising