One-shot/non-retriggerable mode – Basler Electric BE1-11t User Manual

Page 437

Advertising
background image

9424200995 Rev H

425

Figure 272. Pickup/Dropout Mode

Step 10: (Optional.) Repeat steps 1 through 9 for 62-1, 62-2, 62-3, 62-4, 62-5, 62-6, 62-7, and 62-8.

Step 11: (Optional.) Repeat steps 1 through 10 for settings group 1, 2, and 3.

One-Shot/Non-Retriggerable Mode

Step 1: Use BESTCOMSPlus to send the operational settings in Table 198 to the BE1-11t. Retain the

logic settings from Figure 270.

Table 198. Operational Settings (One-Shot/Non-Retriggerable Mode)

Setting

Value

BESTCOMSPlus Screen

Description

62-1 Mode

One-Shot/Non-
Retriggerable

Control, Logic Timers (62)

Sets 62-1 to One-Shot/Non-
Retriggerable mode

62-1 Time
Delay 1 (T1)

400 ms

Control, Logic Timers (62)

Sets 62-1 pickup time delay to
400 ms

62-1 Time
Delay 2 (T2)

20,000 ms

Control, Logic Timers (62)

Sets 62-1 dropout time delay
to 20,000 ms

43-1 Mode

Pulse

Control, Virtual Control
Switches (43)

Sets 43-1 to Pulse mode

62-1 Target

Enabled

Target Configuration,
Targets screen.

Enables 62-1 target

Step 2: Step 4 supplies the 62-1 timer with a momentary initiate input by pulsing the 43-1 switch from

an OFF state to an ON state and then back to an OFF state. You can view the state changes of
the 43-1 switch at the Metering > Control > Virtual Switches screen on the front-panel display.

Step 3: Close communication with BESTCOMSPlus.

Note

The 43-1 switch action is performed twice in this test. To illustrate the
action of the timer mode, step 4 should be executed as quickly as
possible. Ideally, this test should be repeated within 20 seconds. If this
is a problem, try extending the dropout timer setting (Time Delay 2).

Step 4: Using the front-panel display, navigate to Metering > Control > Virtual Switches. Highlight the

first switch (43-1) and press the Right key on the front panel to enter the 43-1 control screen.
Use the Edit key to login. Highlight Operate and then press the Edit key to change the state of
the 43-1. Using the Up/Down keys select PUL and then press the Edit key.

Step 5: Use the Metering Explorer in BESTCOMSPlus to open the Reports, Sequence of Events

screen. Verify that an OFF-ON-OFF pulse action was logged and that approximately 400 ms
after the initial 43-1 OFF-ON-OFF initiate signal action, the 62-1 timer output went true. Then,
approximately 20 seconds later, time delay 2 expired and the 62-1 timer output went false

P

0

0

3

5

-3

0

0

2

-2

7

-0

6

62-x

Block

Initiate

BE1-11t

Logic Timers (62) Test